Предлагаем вам купить "6AG2136-6AB00-1CA1
по выгодной цене оптом или в розницу. Артикул данного товара - "6AG2136-6AB00-1CA1", бренд – "Siemens". Мы осуществляем доставку по Москве и всей России; гарантируем доставку товара в срок. После оформления заказа, наша команда свяжется с Вами для подтверждения заказа и уточнения деталей доставки. Если у Вас возникли вопросы или требуется помощь в выборе товара, Вы можете связаться с нашим отделом продаж.
6AG2136-6AB00-1CA1, 6AG2136 6AB00 1CA1
24 V encoder supply |
Output current, max |
300mA; total current of all encoders/channels |
Short-circuit protection |
Yes |
24 V encoder supply |
24 V |
Yes; min. L+ (-1.5 V) |
Address space per module |
Outputs |
5byte; S7-300/400F CPU, 4 byte |
Address space per module |
Inputs |
14byte; S7-300/400F CPU, 13 byte |
Alarms |
Limit value alarm |
No |
Alarms |
Diagnostic alarm |
Yes |
Altitude during operation relating to sea level |
Ambient air temperature-barometric pressure-altitude |
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Altitude during operation relating to sea level |
Installation altitude above sea level, max |
2000m |
Ambient temperature during operation |
horizontal installation, max |
60C; = Tmax; +70 C for 10 min (OT1, ST1/ST2 acc. to EN 50155); +70 C continuously with configured slots to the left and right of the module (OT3, ST1/ST2 acc. to EN 50155) |
Ambient temperature during operation |
horizontal installation, min |
-30C; = Tmin (incl. condensation/frost) |
vertical installation, min |
-30C; = Tmin |
Ambient temperature during operation |
vertical installation, max |
50C; = Tmax |
Analog inputs |
For current measurement |
|
Analog inputs |
Number of analog inputs |
4 |
Analog value generation for the inputs |
Measurement principle |
Sigma Delta |
Automatic encoding |
Electronic coding element type F |
|
Cable length |
shielded, max |
200m |
CiR - Configuration in RUN |
Calibration possible in RUN |
No |
Reparameterization possible in RUN |
No |
Common mode voltage, max |
Common mode interference, min |
70dB |
Conformal coating |
Coatings for printed circuit board assemblies acc. to EN 61086 |
Yes; Class 2 for high reliability |
Military testing according to MIL-I-46058C, Amendment 7 |
Yes; Discoloration of coating possible during service life |
Protection against fouling acc. to EN 60664-3 |
Yes; Type 1 protection |
Conformal coating |
Electronic equipment on rolling stock acc. to EN 50155 |
Yes; Class PC2 protective coating acc. to EN 50155:2017 |
Conformal coating |
Qualification and Performance of Electrical Insulating Compound |
Yes; Conformal coating, Class A |
Coolants and lubricants |
Resistant to commercially available coolants and lubricants |
Yes; Incl. diesel and oil droplets in the air |
Diagnoses |
Monitoring the supply voltage |
Yes |
Diagnostics indication LED |
for channel diagnostics |
Yes; red LED |
Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
RUN LED |
Yes; green LED |
Diagnostics indication LED |
ERROR LED |
Yes; red LED |
Diagnostics indication LED |
Channel status display |
Yes; green LED |
for module diagnostics |
Yes; green/red DIAG LED |
Dimensions |
Depth |
58mm |
Height |
73mm |
Width |
15mm |
Errors/accuracies |
Temperature error (relative to input range), (+/-) |
0.023%/K |
Errors/accuracies |
Repeat accuracy in steady state at 25 C (relative to input range |
0.1% |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.1% |
Firmware version |
Color code for module-specific color identification plate |
CC00 |
FW update possible |
Yes |
usable BaseUnits |
BU type A0, A1 |
for voltage measurement |
Burden of 2-wire transmitter, max |
|
for current measurement as 2-wire transducer |
|
for current measurement as 4-wire transducer |
|
General information |
Product type designation |
F-AI 4XU 0..10V HF |
Highest safety class achievable in safety mode |
Category according to ISO 13849-1 |
Cat. 4 |
Highest safety class achievable in safety mode |
SIL in accordance with EN 50126, 50128, 50129 |
SIL 2; a higher safety integrity level is possible if tested and approved for the specific application under consideration of all local regulations |
Highest safety class achievable in safety mode |
Performance level according to ISO 13849-1 |
PLe |
SIL acc. to IEC 61508 |
SIL 3 |
Input current |
Current consumption (rated value) |
0.38A |
Current consumption, max |
0.4A |
Input ranges (rated values), currents |
4 mA to 20 mA |
|
Input ranges (rated values), currents |
Input resistance (0 to 20 mA) |
|
Input resistance (4 mA to 20 mA) |
|
Input ranges (rated values), currents |
0 to 20 mA |
|
Integration and conversion time/resolution per channel |
Interference voltage suppression for interference frequency f1 i |
50 / 60 Hz |
Integration and conversion time/resolution per channel |
Integration time (ms) |
20 / 16,667 |
Integration and conversion time/resolution per channel |
Integration time, parameterizable |
Yes |
Resolution with overrange (bit including sign), max |
16bit |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = |
Series mode interference (peak value of interference < rated |
40dB |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Isolation |
Isolation tested with |
750 V DC (type test) and according to EN 50155 (routine test) |
Other |
Note: |
for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776 |
permissible input voltage for voltage input (destruction limit), |
permissible input current for current input (destruction limit), |
|
Permissible potential difference |
between the inputs (UCM) |
10 Vpp |
Potential separation channels |
between the channels |
No |
between the channels and backplane bus |
Yes |
between the channels and the power supply of the electronics |
Yes |
Power |
Power available from the backplane bus |
70mW |
Power loss |
Power loss, typ |
2W |
Probability of failure (for service life of 20 years and repair |
High demand/continuous mode: PFH in accordance with SIL3 |
< 1.00E-09 1/h |
Low demand mode: PFDavg in accordance with SIL3 |
< 5.00E-05 |
Product function |
I&M data |
Yes; I&M0 to I&M3 |
Railway application |
EN 50121-3-2 |
Yes; EMC for rail vehicles |
EN 50124-1 |
Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
EN 50125-2 |
Yes; Stationary electrical equipment - see ambient conditions |
Fire protection acc. to EN 45545-2 |
Yes; For proof of conformity, see Service & Support |
Railway application |
EN 50125-1 |
Yes; Rail vehicles - see ambient conditions |
EN 50125-3 |
Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
EN 61373 |
Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
Railway application |
EN 50121-4 |
Yes; EMC for signal and telecommunications systems |
EN 50155 |
Yes; Rail vehicles - temperature class OT1, ST1/ST2, horizontal mounting position |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max |
100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Remark |
Note regarding classification of environmental conditions acc. t |
* The supplied plug covers must remain in place over the unused interfaces during operation! |
Smoothing of measured values |
Number of smoothing levels |
7 |
Smoothing of measured values |
parameterizable |
Yes |
Step: High |
Yes; 32x / 64x conversion cycle time |
Step: low |
Yes; 2x / 4x conversion cycle time |
Step: Medium |
Yes; 8x / 16x conversion cycle time |
Step: None |
Yes; 1x conversion cycle time |
Supply voltage |
permissible range, lower limit (DC) |
19.2V |
permissible range, upper limit (DC) |
28.8V |
Rated value (DC) |
24V |
Supply voltage |
Reverse polarity protection |
Yes |
Usage in industrial process technology |
Against chemically active substances acc. to EN 60654-4 |
Yes; Class 3 (excluding trichlorethylene) |
Environmental conditions for process, measuring and control syst |
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Use in stationary industrial systems |
Against mechanical environmental conditions acc. to EN 60721-3-3 |
Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
to biologically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
to chemically active substances according to EN 60721-3-3 |
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3S4 incl. sand, dust, * |
Use on land craft, rail vehicles and special-purpose vehicles |
Against mechanical environmental conditions acc. to EN 60721-3-5 |
Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
against mechanical environmental conditions in agriculture acc. |
Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
to biologically active substances according to EN 60721-3-5 |
Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
to chemically active substances according to EN 60721-3-5 |
Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
to mechanically active substances according to EN 60721-3-5 |
Yes; Class 5S3 incl. sand, dust; * |
Voltage, relative to input range, (+/-) |
Current, relative to input range, (+/-) |
|
Weights |
Weight, approx |
48g |