Предлагаем вам купить "6BK1943-2AH00-0AA0
по выгодной цене оптом или в розницу. Артикул данного товара - "6BK1943-2AH00-0AA0", бренд – "Siemens". Мы осуществляем доставку по Москве и всей России; гарантируем доставку товара в срок. После оформления заказа, наша команда свяжется с Вами для подтверждения заказа и уточнения деталей доставки. Если у Вас возникли вопросы или требуется помощь в выборе товара, Вы можете связаться с нашим отделом продаж.
6BK1943-2AH00-0AA0, 6BK1943 2AH00 0AA0
4th output voltage for heating power |
Design of overvoltage protection |
Transil Diode |
Design of short-circuit protection per output |
Melting fuse 32 A |
for heating elements with high inrush current, max |
6000W; At 400 V AC |
Melting I2t value |
250A |
Output current for heating power |
32A; max |
Power carrying capacity per output, max |
12800W; At 400 V AC |
Power carrying capacity per output, min |
1200W; At 400 V AC |
Air pressure acc. to IEC 60068-2-13 |
Storage, min |
660hPa |
Air pressure acc. to IEC 60068-2-13 |
Operation, max |
1080hPa |
Operation, min |
860hPa |
Air pressure acc. to IEC 60068-2-13 |
Storage, max |
1080hPa |
Altitude during operation relating to sea level |
Installation altitude above sea level, max |
2000m |
Ambient temperature during operation |
max |
55C |
min |
0C |
Ambient temperature during storage/transportation |
Storage, max |
70C |
Storage, min |
-25C |
Ambient temperature during storage/transportation |
Transportation, min |
-25C |
Ambient temperature during storage/transportation |
Transportation, max |
70C |
Connection method |
Connectable conductor cross-sections for AWG cables, stranded |
1x (18 ... 4) |
Connectable conductor cross-sections, finely stranded with wire |
1x (0.75 ... 16 mm |
Connectable conductor cross-sections, solid |
1x (0.75 ... 16 mm |
Design of electrical connection at output for heating and fan |
plug, 3-pole, with operating lever, push-in |
Design of electrical connection for supply voltage |
Busbar adapter, 3-pole + N + PE |
Control of heating elements |
Soft start |
Yes |
Control of heating elements |
Half-wave control |
Yes |
Phase control |
Yes |
Degree and class of protection |
IP degree of protection |
IP20 |
Diagnoses |
Communication error |
Yes |
Frequency outside the permissible range |
Yes |
Line voltage outside the permissible range |
Yes |
Parallel-connected heating elements |
Yes |
Rotating field fault |
Yes |
Triac error |
Yes |
Diagnoses |
Fault current too high |
Yes |
Load failure |
Yes |
Supply voltage not connected |
Yes |
Switch-off threshold for internal device temperature |
Yes |
Dimensions |
Depth |
250mm |
Height |
340mm |
Width |
104mm |
EMC |
Conducted interference due to surge acc. to IEC 61000-4-5 |
on supply and load lines: 1 kV symmetric, 2 kV unsymmetric |
EMC |
Conducted interference due to high-frequency radiation acc. to I |
10 V (0.15 ... 80 MHz) |
EMC |
EMC interference emission |
Limit value in accordance with IEC 61000-6-4:2007 + A1:2011 |
EMC |
Conducted interference due to burst acc. to IEC 61000-4-4 |
2 kV power supply lines, 2 kV load lines |
Electrostatic discharge acc. to IEC 61000-4-2 |
4 kV contact discharge / 8 kV air discharge |
Field-related interference acc. to IEC 61000-4-3 |
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
For phase against neutral with fan at 40 C, max |
Switching capacity current per phase, max |
83A |
General information |
Product type designation |
POM4320 Highend |
Heating power |
2nd output voltage for heating power |
277V |
Heating power |
Number of digital outputs |
6; Possible parallel switching of 2 outputs |
Number of heating elements per output, max |
5 |
Output voltage for heating power |
230V |
Input voltage |
device version of the power supply for electronics |
Power supply via CIM |
Installation type/mounting |
Mounting type |
Busbar mounting |
Type of ventilation |
Self-ventilation |
Installation type/mounting |
Mounting position |
vertical |
Interfaces |
Interfaces/bus type |
system interface |
Interrupts/diagnostics/status information |
LED status display |
LED green = ready, LED yellow = heating on/off, LED red = error display, LED red = error for each channel |
Number of status displays |
9 |
Interrupts/diagnostics/status information |
Diagnostics function |
Voltage and current diagnosis |
Isolation |
Overvoltage category |
III |
Isolation |
Degree of pollution |
2 |
Line frequency |
Rated value 50 Hz |
Yes |
Rated value 60 Hz |
Yes |
Line frequency |
Relative symmetrical tolerance |
5% |
Load connection type |
2-pole switching |
Yes; Phase - phase |
closed delta connection (2-phase) |
Yes; Economy circuit |
Closed delta connection (3-phase) |
Yes |
Open delta connection (single-phase) |
Yes; Incoming fuse in the device optionally possible |
Star connection with neutral conductor (2-phase) |
Yes; Economy circuit |
Star connection with neutral conductor (single-phase) |
Yes |
star connection without neutral conductor (3-phase) |
Yes |
Mains buffering |
Recovery time after power failure, typ |
1s |
Measuring functions |
Current measurement |
Yes |
Fault current detection |
Yes; For 2-pole switching |
Voltage measurement |
Yes |
Monitoring functions |
Temperature monitoring |
Yes |
Monitoring functions |
Type of temperature monitoring |
NTC thermistor |
Potential separation |
Design of electrical isolation |
Optocoupler and/or protective impedance between main circuit and PELV |
Potential separation |
between the outputs |
No |
Power |
Active power input, max |
10W |
Power electronics |
Type of load |
Ohmic load |
Power electronics |
For phase against phase with fan at 40 C, max |
76.8kW; At 400 V AC |
Power capacity, max |
76.8kW; At 400 V AC |
Relative humidity |
Operation at 50 ℃, max |
50%; 95 % at 25 C, decreasing linearly to 50 % at 50 C |
Relative humidity |
Operation at 25 ℃, max |
95% |
Setpoint input |
Percent |
Yes |
Shock testing |
Shock resistance during operation acc. to IEC 60068-2-27 |
15 g / 11 ms / 3 shocks/axis |
Shock testing |
Shock resistance during storage acc. to IEC 60068-2-29 |
25 g / 6 ms / 1 000 shocks/axis |
Standards, approvals, certificates |
UL approval |
No |
Standards, approvals, certificates |
CE mark |
Yes |
China RoHS compliance |
Yes |
EAC (formerly Gost-R) |
Yes |
KC approval |
Yes |
RCM (formerly C-TICK) |
Yes |
reference designation according to IEC 81346-2 (2009) |
Q |
Supply voltage |
Rated value (AC) |
230V; phase - neutral conductor |
Supply voltage |
Type of supply voltage |
AC |
Supply voltage |
2nd rated value (AC) |
277V; phase - neutral conductor |
Relative negative tolerance |
25% |
Relative positive tolerance |
8% |
Vibrations |
Vibration resistance during operation acc. to IEC 60068-2-6 |
10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g |
Vibration resistance during storage acc. to IEC 60068-2-6 |
5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g |